Features:
• Heavy Duty Stainless Steel Module Receptacle Housing Resists Corrosion & Abuse
• UL Listed Circuit Breaker Protects Operator & Equipment
• Nickel Plated Brass Contacts & Unique Outlet Design Resists Corrosion & Arc Tracking
|
| Rating: |
Receptacle - 60A 240VAC
Circuit Breaker - 50A Trip / 65,000AIC @ 240VAC
Environmental - IP67 per IEC 529 / IEC 309-1 Type 4X capable per NEMA 250, UL 50/508, CSA 22.2 (with mated plug or screw cover)
Terminals - (3) Phase & (1) Ground pressure type screw terminal
Phase: #10 - #4 AWG (4-25mm2) Wire Range
Ground: #10 - #4 AWG (4-25mm2) Wire Range |
| Materials: |
Stainless Steel - Frame, On/Off Rod, Interlock Mechanism, Contact Terminal Screws & Spring, Snap Cover, Receptacle Housing and all Fasteners
Thermoplastic Polyester (PET) - Contact Carrier
Brass Nickel Plated - Contact Sleeves
Thermoplastic Polyester (PET) - Screw Cover
Neoprene (CR) - Gaskets, Cover Seals
Buna-N (Nitrile/NBR) - O-Rings |
| Approvals: |
UL Listed Module • UL 489 Listed / CSA Certified Molded Case Circuit Breaker |
| Accesories & Parts: |
• Stainless Steel Snap Cover Assy 1501-35
• Circuit Breaker 4020-06
• Screw Cover & Tether Assy 1500-14
• Receptacle & Contact Sleeve Assy 2000-32A |