ESL’s ERTG Safety-interlocked, Fused Disconnect Cabinet provides safe power connections for Electrical Rubber Tire Gantries at container terminals and other medium-voltage applications.
• 12GA 304 Stainless Steel Construction Resists Corrosion & Abuse
• Mechanically Interlocked 5kV Switch, Door and Receptacle Prevents Energizing the Receptacle Without Plug Inserted or Disengaging of the Plug while Switch is “ON” and Ungrounded
• 7.2kV Cavotec™ Push & Pull Receptacle
Internal Earthing Switch (Once 5kV is Open) Prevents Removing Plug Prior to Grounding Out Residual Voltage
Rating:
5kV Switch - Max Rated Voltage of 8.25kV. Rated BIL of 75kVBIL.
Continuous and Loadbreak Amperage of 200A. Momentary
Rating is 40kA RMS
Receptacle - Cavotec PC5-VX4-K0350L, 150A
Environmental - IP56 per IEC 529
Type 3R capable per NEMA 250, UL 50, CSA 22.2
Terminals - Receptacles - (3) Phase, (1) Ground & (2) Pilot Pins
Mainswitch - (3) Phase, (1) Ground (250kcmil - #6AWG)